Municipal Wastewater Regulation, B.C. Reg. 87/2012

Section 60

Failed water toxicity tests

Cite as Municipal Wastewater Regulation, B.C. Reg. 87/2012, s. 60 · last amended October 27, 2025 · read from BC Laws on November 17, 2026

The text

(1) If a discharge fails a routine toxicity test under section 58 [toxicity monitoring requirements], the discharger must (a) notify a director immediately, and (b) conduct a confirmation toxicity test within 14 days of the date the previous toxicity sample was taken. (2) When conducting a confirmation toxicity test or when monitoring after a confirmed failure of a toxicity test, a discharger must (a) monitor ammonia levels at the same time, and (b) record the temperature and pH of the sample at the time of sampling. (3) If a discharge fails 2 consecutive toxicity tests, the discharger must conduct monitoring at the frequency specified in Column 3 of Table 2 in section 58 until the discharge passes 3 consecutive toxicity tests, after which time testing reverts to the frequency specified in Column 2 of that table.
Read the Municipal Wastewater Regulation on BC Laws ↗

Made under Environmental Management Act, SBC 2003, c. 53.