Municipal Wastewater Regulation, B.C. Reg. 87/2012
Section 118
Monitoring requirements for reclaimed water
Cite as Municipal Wastewater Regulation, B.C. Reg. 87/2012, s. 118 · last amended October 27, 2025 · read from BC Laws on November 17, 2026
The text
(1) A provider of reclaimed water must monitor the applicable discharge quality and quantity in accordance with this section and Table 14.
(2) A provider of reclaimed water must monitor groundwater levels and water flows to ensure that reclaimed water use, or an alternate method of discharge, is managed to avoid adverse effects.
(3) A provider of reclaimed water must submit reports as follows:
(a) for reclaimed water categorized as having indirect potable use, weekly;
(b) for reclaimed water categorized as having greater exposure potential, monthly;
(c) for reclaimed water categorized as having moderate or lower exposure potential, quarterly.
(4) Despite subsection (3), a director may authorize reports to be submitted less often than is required under that subsection.
Table 14 — Monitoring Requirements For Reclaimed Water Parameters Indirect
Potable Reuse Exposure Potential Greater Moderate Lower pH site specific weekly weekly weekly CBOD5, TSS, flow volume weekly weekly weekly weekly turbidity continuous
monitoring continuous
monitoring n/a n/a fecal coliform daily daily weekly weekly
Read the Municipal Wastewater Regulation on BC Laws ↗
Made under Environmental Management Act, SBC 2003, c. 53.