Municipal Wastewater Regulation, B.C. Reg. 87/2012
Section 110
Additional requirements if greater exposure potential
Cite as Municipal Wastewater Regulation, B.C. Reg. 87/2012, s. 110 · last amended October 27, 2025 · read from BC Laws on November 17, 2026
The text
(1) This section applies to municipal effluent quality requirements only if the use of reclaimed water is categorized as having greater exposure potential.
(2) To remove viruses, a provider of reclaimed water must do one or more of the following:
(a) provide for the chemical addition of a coagulant or polymer, followed by filtration;
(b) provide for 60-day storage after secondary treatment, if
(i) municipal effluent quality requirements are met after storage and treatment,
(ii) no short circuiting is occurring or likely to occur, and
(iii) no viruses at levels of concern to a health officer are detected in the reclaimed water;
(c) provide an equivalent form of treatment that is authorized by a director.
(3) In respect of fecal coliform monitoring,
(a) based on an initial 60 days of compliance with the daily fecal coliform quality limit, a provider of reclaimed water may conduct weekly fecal coliform testing, and
(b) if the presence of fecal coliform is detected, daily testing must be reinstated and 7 consecutive non-detect results must be achieved before weekly testing may be resumed.
(4) If ground discharge is the alternate disposal method and 5 years have elapsed without issue, the constructed drainage pipe length as specified in section 78 [drainage pipe length requirements] may be reduced if
(a) recommended by a suitably qualified professional, and
(b) a director authorizes the reduction.
Read the Municipal Wastewater Regulation on BC Laws ↗
Made under Environmental Management Act, SBC 2003, c. 53.