Processing Facility Regulation, B.C. Reg. 48/2021

Section 8

Storage system

Cite as Processing Facility Regulation, B.C. Reg. 48/2021, s. 8 · last amended March 10, 2026 · read from BC Laws on November 17, 2026

The text

(1) A processing facility permit holder must ensure that the engineering design of a storage system conforms to the requirements of this section. (2) A storage system must provide for both of the following: (a) the safe storage in tanks of energy resources, the products of energy resources, carbon dioxide and any other solids and fluids, including waste; (b) the protection of the storage system from failure, taking into account the design fatigue life of the system equipment. (3) The storage system must include spill containment designed to (a) prevent spills of solids or fluids from leaving the containment area, and (b) minimize the pooling of spilled solids or fluids that may endanger the safe operation of the processing facility. (4) To prevent leaks from a liquid storage tank, other than a pressurized vessel, from leaving the containment area, the storage system must have an impermeable secondary containment system that has a capacity of at least the following: (a) if secondary containment includes one tank only, 110% of the tank's capacity; (b) if secondary containment includes multiple tanks, the sum of the capacity of the largest tank plus the greater of the following: (i) 10% of the capacity of the largest tank; (ii) 10% of the total capacity of all other tanks in the secondary containment system.
Read the Processing Facility Regulation on BC Laws ↗

Made under Energy Resource Activities Act, SBC 2008, c. 36.