Occupational Health and Safety Regulation, B.C. Reg. 296/97
Schedule 14-A
Schedule 14-A
Cite as Occupational Health and Safety Regulation, B.C. Reg. 296/97, Schedule 14-A · last amended September 1, 2027 · read from BC Laws on November 17, 2026
The text
Schedule 14-A
[en. B.C. Reg. 188/2011, App. L, s. 6.]
(sections 14.2 (9), 14.116 and 14.117)
WorkSafeBC Standard 14.116 — Chimney Hoists 1 This standard sets out the minimum requirements that are in addition to those set out in sections 14.116 to 14.119 of this Regulation for the design and use of a chimney hoist to transport personnel to a fixed work platform on a chimney or similar structure. 2
(1) In this standard:
“cage” means the fully enclosed platform of a chimney hoist, which platform is used to raise or lower one or more persons to a fixed work platform on a chimney or similar structure;
“hoist”, in respect of a chimney hoist, means the apparatus that is used to raise or lower the cage;
“rated capacity”, in respect of a cage or a hoist, means the maximum weight the cage or hoist is rated by its manufacturer to carry.
(2) The definitions set out in ANSI/ASSE Standard A10.22-2007, Safety Requirements for Rope-Guided and Non-Guided Workers' Hoists, apply in this standard. 3
(1) A chimney hoist must
(a) be designed, constructed, erected, disassembled, inspected, maintained and operated as specified by the manufacturer or a professional engineer, and
(b) meet the requirements of ANSI/ASSE Standard A10.22-2007, Safety Requirements for Rope-Guided and Non-Guided Workers' Hoists, except as otherwise specified in this standard.
(2) A chimney hoist must have a cage. 4
(1) Following any alteration to a chimney hoist, other than ordinary adjustments or repairs,
(a) the chimney hoist must be tested by a professional engineer and certified as required under section 14.117 of this Regulation, and
(b) the design documents and operating instructions must be updated by the professional engineer as necessary to ensure the documentation is complete and allows for safe use of the chimney hoist.
(2) A copy of the certification required under subsection (1) must be available at the workplace where the chimney hoist is installed. 5 A chimney hoist must be outfitted with emergency stopping devices on at least two separate guide wire ropes that will apply automatically to prevent the cage from falling if a wire rope fails. 6 Suspension and guide wire ropes, supporting structures, slings and metal fittings used on a chimney hoist must have a safety factor of 10. 7 A hoist must have a positive drive and there must not be a clutch between the transmission and the hoist drum. 8 A hoist must have two independent braking systems: one that applies automatically when the controls are in the neutral position, and one that applies automatically in the event of loss of power. 9 A chimney hoist must have upper and lower terminal stopping devices that automatically stop the cage from normal travel speed, within the top and bottom travel limits. 10 A hoist must have a governing device that will effectively prevent the drum speed from exceeding 110% of the design speed. 11 The hoist, wire ropes and cage of a chimney hoist must be in good working order with all components, controls and functions meeting, and operating in accordance with, the manufacturer's specifications, the professional engineer's design specifications and this Regulation. 12 The cage must be legibly marked to show
(a) the name of the manufacturer or certifying professional engineer,
(b) a unique identification number or code that links to the design and certification documentation for the chimney hoist from the certifying professional engineer,
(c) the weight of the cage, and
(d) the rated capacity of the cage. 13
(1) The rated capacity of the cage must not be exceeded.
(2) A chimney hoist must not use a hoist with a rated capacity that is less than the rated capacity of its cage. 14 The cage must be constructed so that
(a) it does not cause a hazard to the occupants, and
(b) the occupants cannot reach any hazard created by movement of the cage or the hoisting mechanism. 15 A landing that is 3 m (10 ft) or more above grade must have gates, hinged guardrails, hinged covers or other effective guarding that protects persons who are at or near the landing from the hazard of falling off of or through the landing platform when the cage is not at that landing. 16 The lower landing for a chimney hoist must be guarded by perimeter guards or guardrails and a gate. 17 The instructions from the professional engineer who designed the chimney hoist and from the manufacturers of its component parts, relating to safe use and maintenance of the chimney hoist, must be available in the workplace. 18 The chimney hoist, including its cage, must be in good condition at the beginning of each shift and during use. 19
(1) A chimney hoist operator must not operate a chimney hoist unless authorized by the employer.
(2) A chimney hoist operator must not be authorized under subsection (1) unless the operator has demonstrated
(a) competency in the operation of the chimney hoist, and
(b) familiarity with the operating instructions required under section 17 and the communication systems required under sections 22 and 23. 20 Before the first use on each work shift, the cage of the chimney hoist must be raised to its maximum operating height and lowered back to the ground or base to ensure that
(a) all functions are operating correctly,
(b) all limit devices are functioning properly, and
(c) there is adequate clearance between the cage and any surrounding object such as a structure, overhead obstruction, storage rack, or scaffold, and any hazard such as energized electrical wires and equipment. 21 The operator of a chimney hoist must not leave the hoist controls unattended or engage in any other tasks unless the cage is at the lowest landing level, which is usually at ground or grade level, and no persons are in the cage. 22
(1) There must be effective voice communication, using single channel two-way radios, among the chimney hoist operator, occupants of the cage and people at each hoist landing.
(2) If there is more than one occupant in a cage, one person in the cage must be designated to be the primary person to signal the chimney hoist operator regarding cage movement requests. 23
(1) An effective signalling system must be developed and implemented as an alternative in the event the primary voice communication system becomes ineffective while the chimney hoist is in use.
(2) If the voice communication system becomes ineffective while the chimney hoist is in use, the signalling system required under subsection (1) must be used to bring the cage down to the lowest landing and the hoist must not be used until the voice communication system is effectively restored. 24 Materials, equipment or supplies must not be raised or lowered by the chimney hoist with a person in the cage. 25 The cage must be at a designated landing before a person gets into or out of the cage. 26 A cage must not be raised or lowered at a speed greater than 76 m/min (250 fpm). 27 All the gates of a chimney hoist must be kept closed, except at a landing designated for loading and unloading the cage. 28
(1) Before a chimney hoist is used, a plan must be developed for the evacuation of personnel from the cage in the event of loss of power or equipment malfunction.
(2) While a chimney hoist is in use, personnel and equipment must be immediately available to implement the plan required under subsection (1).
Read the Occupational Health and Safety Regulation on BC Laws ↗
Made under Workers Compensation Act, RSBC 2019, c. 1.