Occupational Health and Safety Regulation, B.C. Reg. 296/97

Section 9.32

Mechanical ventilation

Cite as Occupational Health and Safety Regulation, B.C. Reg. 296/97, s. 9.32 · last amended September 1, 2027 · read from BC Laws on November 17, 2026

The text

(1) A ventilation system for the control of airborne contaminants in a confined space must be designed, installed and maintained in accordance with established engineering principles and must be specified in the written procedures. (2) Ventilation equipment must be located and arranged so as to adequately ventilate every occupied area inside the confined space. (3) If a contaminant is produced in a confined space, it must be controlled at the source by a local exhaust ventilation system if practicable, by general (dilution) ventilation, or by a combination of both. (4) If practicable, a mechanical ventilation system for a confined space must be sufficient to maintain concentrations of airborne contaminants below the applicable exposure limits.
Read the Occupational Health and Safety Regulation on BC Laws ↗

Made under Workers Compensation Act, RSBC 2019, c. 1.