The text
(1) A tank truck must be electrically bonded and grounded when loading and unloading hydrocarbons.
(2) The ground conductor required by subsection (1) must remain effectively attached until all other connections have been removed.
(3) Servicing or maintenance must not be carried out on a tank truck when loading or unloading hydrocarbons except for required greasing of the pump.
(4) Chocks must be used to secure a tank truck while loading and unloading hydrocarbons.
(5) Other vehicles must not be started or shut off within 8 m (25 ft.) of a tank truck containing flammable liquids while it is being connected or disconnected.
(6) If a tank truck is being loaded through a dome hatch and it is necessary to observe the fluid level
(a) a platform must be provided for the loader,
(b) shutoff controls must be located at the platform,
(c) illumination in accordance with the requirements of Part 4 [General Conditions] must be provided during hours of darkness, and
(d) the loading spout must extend to within l5 cm (6 in.) of the bottom of the tank.
Read the Occupational Health and Safety Regulation on BC Laws ↗
Made under Workers Compensation Act, RSBC 2019, c. 1.