Occupational Health and Safety Regulation, B.C. Reg. 296/97
Section 22.28
Heating equipment
Cite as Occupational Health and Safety Regulation, B.C. Reg. 296/97, s. 22.28 · last amended September 1, 2027 · read from BC Laws on November 17, 2026
The text
(1) The installation of underground heating equipment acceptable to the Board must include provisions for mounting, clearances and air supply, and must meet the applicable requirements of the following standards and codes as amended from time to time:
(a) CSA Standard CAN/CSA-B139-M91, Installation Code for Oil Burning Equipment;
(b) CGA Code CAN/CGA-B149.1-M91, Natural Gas Installation Code;
(c) CGA Code CAN/CGA-B149.2-M91, Propane Installation Code;
(d) CSA Standard C22.1-94, Canadian Electrical Code, Part 1;
(e) CSA Standard B51-M1991, Boiler, Pressure Vessel, and Pressure Piping Code.
(2) With the exception of embedded pipes or ducts, all parts of the heating system must be readily accessible for inspection, maintenance, repair and cleaning.
(3) The heating system must be protected from freezing.
(4) A carbon monoxide detector, capable of detecting concentrations below 25 ppm and shutting down the heater if this level is exceeded, must be installed 15 m (50 ft) downstream from where the heated air enters the underground working.
(5) Pipelines with gas pressures in excess of 3.5 kPa (0.5 psi) must not be located within 15 m (50 ft) of an underground working.
(6) Pressure regulating stations must be clearly marked and protected from physical damage.
(7) Propane storage tanks must be located so that any leak will not enter an underground working.
(8) A vibration switch that will shut down the heater at prescribed vibration limits must be mounted on the fan cage.