Section 22.21

Auxiliary fan

Cite as Occupational Health and Safety Regulation, B.C. Reg. 296/97, s. 22.21 · last amended September 1, 2027 · read from BC Laws on November 17, 2026

The text

The work face must be ventilated by means of an auxiliary fan system which (a) has an air flow of at least 15 cubic metres per minute for each square metre (50 cfm for each square foot) of the working face area, but not more than 90% of the main exhaust system flow, (b) has its inlet overlapping the inlet of the main exhaust system by at least 30 m (100 ft), (c) discharges from within 18 m (60 ft) of the face, unless workers are absent from the face, and (d) has an effective silencer if required by the Board.
Read the Occupational Health and Safety Regulation on BC Laws ↗

Made under Workers Compensation Act, RSBC 2019, c. 1.