Occupational Health and Safety Regulation, B.C. Reg. 296/97
Section 19.18
Isolation and lockout
Cite as Occupational Health and Safety Regulation, B.C. Reg. 296/97, s. 19.18 · last amended September 1, 2027 · read from BC Laws on November 17, 2026
The text
(1) Before working on a power system that for reasons of safety must be de-energized, the worker in charge must ensure that the part of the system being worked on is isolated and grounded, and locked out as required by this Regulation.
(2) Barriers or distinctive identification must be used to differentiate high voltage electrical equipment which has been de-energized for safety reasons from similar energized equipment at the work location if lack of such identification would result in undue risk to workers.
(3) If it is impracticable to lock out a power system or part of the power system
(a) the boundaries of the power system or part must be clearly defined,
(b) written work procedures governing the issue of safety protection guarantees, and which address the requirements of sections 19.19 to 19.23, must be followed, and
(c) all major equipment used to establish safety protection guarantees must be uniquely identified at a conspicuous place on or near the equipment.
Read the Occupational Health and Safety Regulation on BC Laws ↗
Made under Workers Compensation Act, RSBC 2019, c. 1.