Occupational Health and Safety Regulation, B.C. Reg. 296/97

Section 19.16

Isolation and lockout

Cite as Occupational Health and Safety Regulation, B.C. Reg. 296/97, s. 19.16 · last amended September 1, 2027 · read from BC Laws on November 17, 2026

The text

(1) High voltage electrical equipment must, if practicable, be completely isolated, grounded, and locked out as required by this Regulation before starting work on it. (2) If it is not practicable to completely isolate high voltage electrical equipment, (a) written safe work procedures acceptable to the Board must be followed, (b) two or more qualified and authorized persons must be present while the work is being done, unless the procedures being followed under paragraph (a) specifically permit the work to be done by one person, (c) appropriate electrical protective equipment, including rubber blankets, hoses, hoods, gloves and live line tools must be selected, used, stored, tested, and maintained in accordance with a standard acceptable to the Board, and (d) the use of metal ladders, wire reinforced side rail wooden ladders, metal scaffolds or metal work platforms must be in accordance with the procedures established under paragraph (a).
Read the Occupational Health and Safety Regulation on BC Laws ↗

Made under Workers Compensation Act, RSBC 2019, c. 1.