Occupational Health and Safety Regulation, B.C. Reg. 296/97
Section 19.12
Working close to energized equipment
Cite as Occupational Health and Safety Regulation, B.C. Reg. 296/97, s. 19.12 · last amended September 1, 2027 · read from BC Laws on November 17, 2026
The text
(1) Uninsulated, energized parts of low voltage electrical equipment must be guarded by approved cabinets or enclosures unless the energized parts are in a suitable room or similar enclosed area that is only accessible to qualified and authorized persons.
(2) Each entrance to a room and other guarded location containing uninsulated and exposed, energized parts must be marked with a conspicuous warning sign limiting entry to qualified and authorized persons.
(3) If uninsulated energized parts are not guarded with approved cabinets or enclosures
(a) suitable barriers or covers must be provided if a worker unfamiliar with the hazards is working within 1 m (3.3 ft) of the uninsulated, energized parts, or
(b) the worker must be informed of the potential hazards, and provided with and follow appropriate written safe work procedures.
Read the Occupational Health and Safety Regulation on BC Laws ↗
Made under Workers Compensation Act, RSBC 2019, c. 1.