Occupational Health and Safety Regulation, B.C. Reg. 296/97

Section 12.155

Emergency ventilation

Cite as Occupational Health and Safety Regulation, B.C. Reg. 296/97, s. 12.155 · last amended September 1, 2027 · read from BC Laws on November 17, 2026

The text

(1) Supplemental floor level emergency ventilation equipment must be available within 4.6 m (15 ft) of the dry cleaning equipment for use in the event of a spill, leak or accidental release of solvent liquid or solvent vapour. (2) Supplemental ventilating equipment must be capable of changing the air in the dry cleaning area every 5 minutes (12 room-air changes per hour). (3) The control switch for supplemental ventilation equipment must be readily accessible in an emergency, and must be clearly identified by signs or similar means.
Read the Occupational Health and Safety Regulation on BC Laws ↗

Made under Workers Compensation Act, RSBC 2019, c. 1.