Occupational Health and Safety Regulation, B.C. Reg. 296/97
Section 12.132
Air flow
Cite as Occupational Health and Safety Regulation, B.C. Reg. 296/97, s. 12.132 · last amended September 1, 2027 · read from BC Laws on November 17, 2026
The text
(1) The air velocity through a horizontal flow spray booth, a vertical flow, down-draft booth or other enclosure required by section 12.131 must be at least
(a) 50 cm/s (100 fpm) if the cross-sectional area is 14 m2 (150 ft2) or less, and
(b) 25 cm/s (50 fpm) if the cross-sectional area is greater than 14 m2 (150 ft2).
(2) In outdoor applications of materials listed in section 12.131, an air velocity across the work area of at least 0.25 m/s (50 fpm) must be assured, by mechanical means if necessary, to carry vapours and aerosols away from the breathing zone of a worker.
Read the Occupational Health and Safety Regulation on BC Laws ↗
Made under Workers Compensation Act, RSBC 2019, c. 1.