Petroleum Storage and Distribution Facilities Storm Water Regulation, B.C. Reg. 168/94

Section 6

Management of the separator system

Cite as Petroleum Storage and Distribution Facilities Storm Water Regulation, B.C. Reg. 168/94, s. 6 · last amended September 1, 2023 · read from BC Laws on November 17, 2026

The text

(1) Subject to subsection (2), every operator must do all of the following: (a) visually inspect the separator system weekly, looking for any evidence of petroleum bypass or any other condition which might indicate malfunctioning of the separator; (b) take action to correct any malfunction noticed under paragraph (a); (c) measure monthly the thickness of accumulated petroleum on the surface of the separator; (d) measure monthly the thickness of accumulated sludge in the bottom of the separator; (e) measure the thickness of petroleum on the surface of the separator immediately following an accidental discharge of petroleum to the separator; (f) record in the log referred to in subsection (4) (a) (i) the results of the visual inspection required by paragraph (a), (ii) the measurements required by paragraphs (c), (d) and (e), and (iii) the details of any accidental discharge. (2) During periods of extended freezing temperatures, an operator may convert a separator to a spill interceptor by (a) emptying the separator, (b) closing the outlet valve, (c) recording the date that the separator is converted to a spill interceptor and returned to separator operation in the log referred to in subsection (4) (a), and (d) discontinuing the inspections and measurements required under subsection (1) for the period of time that the separator functions as a spill interceptor. (3) After each inspection and measurement required by subsection (1), the operator must (a) immediately remove the accumulated petroleum from the surface of the separator if the accumulated thickness of petroleum exceeds 50 mm, (b) immediately remove the accumulated sludge from the bottom of the separator if the accumulated thickness (i) exceeds 150 mm, or (ii) impairs the operation of the separator, and (c) clean and inspect the separator, regardless of the accumulated thickness of petroleum and sludge, at least once every 2 years. (4) Every operator must maintain, and make available on the request of an officer, the following records: (a) an inspection and cleanout log for the separator which includes the date, visual appearance, measured thickness of oil and sludge layers, volume of oil and sludge removed, name and signature of the person entering the data and, if applicable, the name of the oil and sludge removal contractor; (b) the date and quantity of accidental discharge of petroleum greater than 100 litres into the separator system; (c) a copy of the site plan referred to in section 5 (g). (5) The records required by subsection (4) must be kept for at least 2 years. (6) An operator must not intentionally discharge or allow the intentional discharge of any substance into a separator system unless the substance is (a) water, or (b) water contaminated with hydrocarbon such that the resultant mixture is not waste oil. (7) Notwithstanding subsection (6), an operator must not intentionally discharge or allow the intentional discharge of tank bottom water into a separator system. (8) Every operator must close the separator outlet valve immediately after a petroleum spill is discovered and must not reopen the valve unless the thickness of accumulated petroleum on the surface of the separator is reduced to less than 50 mm. (9) Every operator must institute a preventive maintenance, monitoring and inspection program to prevent the accidental discharge or spillage of petroleum products. (10) The program required by subsection (9) must include monthly or more frequent inspections of the following areas: (a) hoses and nozzles at drum-filling and pump island areas; (b) points at which petroleum is delivered into storage; (c) truck loading racks; (d) the equipment contained in pump cabinets; (e) all visible joints, valves, flanges, and piping. (11) The results of the inspections required by subsection (10) must be maintained in a log format that includes the date, the name and signature of the inspector and a description of the corrective action taken. (12) Every operator must conspicuously display an emergency contact telephone number at all locations where petroleum transfer operations occur. (13) The inspections and actions under subsections (1) and (10) may be suspended after a period of 60 consecutive days during which no petroleum is transferred into or dispensed from the petroleum storage and distribution facility and, if suspended, must resume when petroleum transfer or dispensing is resumed.
Read the Petroleum Storage and Distribution Facilities Storm Water Regulation on BC Laws ↗

Made under Environmental Management Act, SBC 2003, c. 53.