Petroleum Storage and Distribution Facilities Storm Water Regulation, B.C. Reg. 168/94
Section 5
Separator system design
Cite as Petroleum Storage and Distribution Facilities Storm Water Regulation, B.C. Reg. 168/94, s. 5 · last amended September 1, 2023 · read from BC Laws on November 17, 2026
The text
Every operator of a separator system must ensure that the separator system required by section 4 complies with all of the following:
(a) directs to the separator all drainage from a petroleum transfer area;
(b) receives only precipitation runoff, vehicular petroleum discharges and accidental discharges of petroleum from a petroleum transfer area;
(c) is designed and certified, by a professional engineer registered in British Columbia, to provide the hydraulic retention time required to separate droplets greater than 0.015 cm in diameter from storm water or is designed to another standard approved in writing by a director;
(d) is designed to prevent the discharge of an accidental spill by having
(i) a minimum volume of 1 000 litres,
(ii) a shutoff valve on the separator outlet, and
(iii) the capability to sample the effluent discharge from the separator outlet;
(e) is designed for a 10 year return period storm event of 60 minutes duration for the nearest rainfall recording station;
(f) is designed for a water temperature of 5 degrees Celsius and a petroleum specific gravity of 0.85;
(g) is documented on a site plan which shows the location of the separator system, the areas serviced by the storm sewer and the point or points of discharge to the environment;
(h) is constructed in accordance with the design referred to in paragraphs (c), (d), (e) and (f) and as depicted on the site plan referred to in paragraph (g), and certified as such by a professional engineer registered in British Columbia.
Read the Petroleum Storage and Distribution Facilities Storm Water Regulation on BC Laws ↗
Made under Environmental Management Act, SBC 2003, c. 53.