Power Engineers, Boiler, Pressure Vessel and Refrigeration Safety Regulation, B.C. Reg. 104/2004
Section 46
Determination of boiler capacity
Cite as Power Engineers, Boiler, Pressure Vessel and Refrigeration Safety Regulation, B.C. Reg. 104/2004, s. 46 · last amended December 31, 2024 · read from BC Laws on November 17, 2026
The text
(1) In this section, “extended surface” does not include the area of a superheater.
(2) The heat receiving surface area of a boiler must be stated in square metres (m2), must include the extended surface and the heating surface must be computed as follows:
(a) a heating surface, as part of a circulating system in contact on one side with water or wet steam being heated and on the other side with gas or refractory being cooled, must be measured on the side receiving heat;
(b) a boiler heating surface and other equivalent surface outside the furnace must be measured circumferentially plus any extended surface;
(c) a waterwall heating surface and other equivalent surface within the furnace must be measured as the projected tube area (diameter x length) plus any extended surface on the furnace side, but in computing the heating surface for this purpose only the tubes, fireboxes, shells, tubesheets and the projected area of headers need to be considered, except that for vertical firetube steam boilers only that portion of the tube surface up to the middle of the gauge glass is to be computed.
(3) The heat receiving surface area in square metres (m2) of an electric boiler is the number obtained by dividing the maximum kilowatt input by 10.
(4) The heat receiving surface area of a coiltube or a fintube boiler includes the extended surfaces.
(5) Repealed. [B.C. Reg. 170/2018, Sch. 2, s. 21.]
Read the Power Engineers, Boiler, Pressure Vessel and Refrigeration Safety Regulation on BC Laws ↗
Made under Safety Standards Act, SBC 2003, c. 39.