Elevating Devices Safety Regulation, B.C. Reg. 101/2004

Section 39

Stage lifts

Cite as Elevating Devices Safety Regulation, B.C. Reg. 101/2004, s. 39 · last amended March 31, 2022 · read from BC Laws on November 17, 2026

The text

A stage lift must meet the following specifications: (a) a minimum sill clearance of 6 mm must be maintained; (b) the maximum sill clearance is 12 mm; (c) where required, equalization (stabilization) means must be provided to prevent the platform from deflecting more than 9.5 mm from the horizontal when the rated load is placed on any section of the platform; (d) safety locking mechanisms must be provided on all hydraulic stage lifts that do not incorporate an anti-creep device in the design; (e) the safety locking mechanism must engage when the lift is not moving; (f) an electrical interlock must be provided to prevent energization of the operating means in the down direction while the safety locking mechanism is engaged; (g) safety astragals must be installed on the lower perimeter of the platform which, when engaged, will stop the lift in the down direction; (h) a readily identifiable stop switch must be conveniently located in the area below the platform so as to render the anti-creep device inoperative; (i) all shear hazards must be eliminated; (j) all control units must be located to afford a clear view of the lift; (k) all control units must be key operated and incorporate an emergency stop button; (l) a fused lockable type disconnect switch must be located adjacent to the control unit; (m) chains must not be used as a means of suspension.
Read the Elevating Devices Safety Regulation on BC Laws ↗

Made under Safety Standards Act, SBC 2003, c. 39.