Canada Oil and Gas Installations Regulations, SOR/96-118

Section 27

Cite as Canada Oil and Gas Installations Regulations, SOR/96-118, s. 27 · current to July 24, 2025 · regulation last amended October 6, 2020

Statute Watch

Get an alert when a bill in Parliament would change this section, and every time it moves.

The text

(1) The accommodation areas in every manned offshore installation shall be equipped with a sprinkler system that is supplied with water from (a) two dedicated pump systems connected to the water main referred to in section 24 or 25 by way of a lockable screwdown non-return valve that will prevent backflow from the sprinkler system to the water main; or (b) one dedicated sprinkler pump connected to (i) the water main referred to in section 24 or 25 by way of a lockable screwdown non-return valve that will prevent backflow from the sprinkler system to the water main, and (ii) a pressurized fresh water tank having a volume equal to at least twice the volume of water required pursuant to subsection (2) to be supplied for a period of one minute. (2) The volume of water supplied by the pump systems or pump and fresh water tank described in subsection (1) shall be at a pressure sufficient to ensure, at the level of the highest sprinkler, continuous coverage of at least 280 m2 at the rate of at least 6 L/minute/m2. (3) The sprinkler pump required by paragraph (1)(b) shall (a) serve only the sprinkler system; (b) be activated automatically by a pressure drop in the system before the water in the fresh water tank is depleted; and (c) be powered from at least two sources. (4) When the sprinkler system is activated, an audible and visual alarm that shows the location of the activated sprinklers shall be given automatically at the fire and gas indicator panel in the control station. (5) The sprinkler system shall be designed to prevent the passage of sea water into the fresh water tank. (6) The sprinkler system shall be provided with at least one stop valve for every 200 sprinklers that can prevent the flow of water into those sprinklers without affecting the rest of the system. (7) Each of the stop valves provided pursuant to subsection (6) shall be protected from accidental operation. (8) A gauge indicating the pressure in the sprinkler system shall be fitted at each stop valve and at the control station. (9) The sprinkler heads shall be placed in positions and spaced in a pattern that will ensure an average application rate of 6 L/minute/m2 throughout each space in the accommodation areas. (10) The pump system or pump and fresh water tank required by subsection (1) shall be situated outside the accommodation areas and as far as possible from the main machinery space. (11) The sprinkler system shall be (a) installed in accordance with National Fire Protection Association 13, Standard for the Installation of Sprinkler Systems; and (b) tested and maintained in accordance with National Fire Protection Association 13A, Recommended Practice for the Inspection, Testing and Maintenance of Sprinkler Systems.
Read the Canada Oil and Gas Installations Regulations on the Justice Laws Website ↗

Made under Canada Oil and Gas Operations Act, R.S.C. 1985, c. O-7.

Bills in Parliament that would change this section 0

No bill we hold would amend or repeal this section.