Reduction in the Release of Volatile Organic Compounds (Storage and Loading of Volatile Petroleum Liquids) Regulations, SOR/2025-88
Section 92
Baseline LEL%
Cite as Reduction in the Release of Volatile Organic Compounds (Storage and Loading of Volatile Petroleum Liquids) Regulations, SOR/2025-88, s. 92 · current to July 24, 2025 · regulation last amended July 5, 2025
Statute Watch
Get an alert when a bill in Parliament would change this section, and every time it moves.
The text
(1) The operator must calculate a baseline LEL% for the purposes of evaluating the performance of the internal floating roof.
(2) Subject to subsection (3), the baseline LEL% is the arithmetic average of all the values of the LEL% determined in the space above the internal floating roof over the previous four years.
(3) The following values are excluded from the calculation of the baseline LEL%:
(a) all values of the LEL% determined before any total replacement of the primary seal or secondary seal;
(b) all values of the LEL% that exceed 20 or, if the benzene concentration of the volatile petroleum liquid in the tank is greater than or equal to 20% by weight, that exceed 10; and
(c) all values of the LEL% determined before the day on which these Regulations come into force.
(4) Despite subsection (1), there is no established baseline LEL% if there are less than 12 LEL% values included in the calculation.
(5) If there is an established baseline LEL%, the value of the LEL% in the space above the internal floating roof must not exceed the following thresholds:
(a) 150% of the baseline LEL%, if the baseline LEL% is greater than or equal to 5; and
(b) 7.5, if the baseline LEL% is less than 5.
(6) If there is no established baseline LEL%, the value of the LEL% in the space above the internal floating roof must not exceed the following thresholds:
(a) 10, if the tank is a high benzene tank;
(b) 90, if the tank is an inerted tank that is not a high benzene tank; and
(c) 20, in all other cases.
(7) If, during a first inspection, the value of the LEL% exceeds the thresholds set out in subsection (5) or (6) but does not exceed the thresholds set out in paragraphs 101(1)(b) or (c), a second inspection may be performed within seven days after the day of the first inspection and if, during the second inspection, the value of the LEL% does not exceed the applicable thresholds set out in subsection (5) or (6), the value determined during the first inspection is not a defect, despite paragraph 100(5)(d).
Read the Reduction in the Release of Volatile Organic Compounds (Storage and Loading of Volatile Petroleum Liquids) Regulations on the Justice Laws Website ↗
Made under Canadian Environmental Protection Act, 1999, S.C. 1999, c. 33.