The text
(1) The operator of a facility must ensure that each vapour control system at the facility and all piping, tanks, vehicle tanks and other equipment that connect to the vapour space are free of vapour leaks and liquid leaks.
(2) The operator must ensure that all maintenance hatches and other openings to the atmosphere in piping, tanks, vehicle tanks and other equipment that connect to the vapour space are kept sealed during operation of the vapour control system, except during maintenance, inspection or repair.
(3) If the vapour control system is used to control emissions from a tank equipped with a pressure-vacuum vent, the operator must ensure that
(a) the pressure-vacuum vent meets the requirements of section 78 and is inspected and repaired in accordance with sections 104 and 105;
(b) if the vapour control system is a vapour recovery system or a vapour destruction system, the system and the pressure-vacuum vent are designed, used and maintained such that the pressure-vacuum vent remains sealed, except to relieve a vacuum inside the tank or to relieve pressure inside the tank during an emergency situation or a failure of the system; and
(c) if the vapour control system is a vapour balancing system, the system and the pressure-vacuum vent are designed, used and maintained such that the pressure-vacuum vent remains sealed, except to relieve a vacuum inside the tank, to relieve pressure inside the tank in excess of the pressure relief setting set out in paragraph 78(b) or to relieve pressure inside the tank during an emergency situation or a failure of the system.
(4) Subsection (2) does not apply to a temporary vapour control system that has been installed on a tank under subsection 43(1) or (3).