Reduction in the Release of Volatile Organic Compounds (Storage and Loading of Volatile Petroleum Liquids) Regulations, SOR/2025-88

Section 42

Vapour control systems

Cite as Reduction in the Release of Volatile Organic Compounds (Storage and Loading of Volatile Petroleum Liquids) Regulations, SOR/2025-88, s. 42 · current to July 24, 2025 · regulation last amended July 5, 2025

Statute Watch

Get an alert when a bill in Parliament would change this section, and every time it moves.

The text

The operator of a facility must ensure that each loading rack at the facility that is a high benzene loading rack or is designated as a volatile petroleum liquid loading rack under paragraph 13(b) is equipped with one of the following vapour control systems: (a) a vapour recovery system, a vapour destruction system or a vapour balancing system, in the case of a loading rack at a facility where all volatile petroleum liquids loaded, are fuels that are stored either in fixed roof tanks that each have an internal volume of less than 150 m3 or, if the tanks are in the form of a vertically oriented cylinder capable of accommodating a floating roof, an internal diameter of less than 5 m, or in underground tanks of any size; (b) a vapour recovery system, in the case of a loading rack that is used to load gasoline to trucks at a facility where more than 250 000 standard m3 per year of gasoline is loaded per calendar year and that was not equipped with an existing vapour destruction system on the day on which these Regulations came into force; and (c) a vapour recovery system or vapour destruction system, in any other case.
Read the Reduction in the Release of Volatile Organic Compounds (Storage and Loading of Volatile Petroleum Liquids) Regulations on the Justice Laws Website ↗

Made under Canadian Environmental Protection Act, 1999, S.C. 1999, c. 33.