Reduction in the Release of Volatile Organic Compounds (Storage and Loading of Volatile Petroleum Liquids) Regulations, SOR/2025-88

Section 28

Combustible gas detector — requirements

Cite as Reduction in the Release of Volatile Organic Compounds (Storage and Loading of Volatile Petroleum Liquids) Regulations, SOR/2025-88, s. 28 · current to July 24, 2025 · regulation last amended July 5, 2025

Statute Watch

Get an alert when a bill in Parliament would change this section, and every time it moves.

The text

(1) A combustible gas detector that uses a catalytic bead sensor must meet the following requirements: (a) each day before it is used, it must be calibrated in accordance with its design specifications using output correction factors, if necessary, and a calibration gas that are appropriate for the expected vapour composition; (b) it must produce an output directly as an LEL%; (c) it must have an output range that spans an LEL% of at least 1 to 100; and (d) it must have an output accuracy that is within plus or minus 5% of a reading or plus or minus LEL% of 2, whichever value is greater, when used with the expected vapour composition. (2) A combustible gas detector that uses a catalytic bead sensor must not be used in the following environments: (a) an atmosphere that contains less than 10% oxygen by volume; (b) an atmosphere that contains substances that are likely to poison the catalyst; or (c) any other environment in which, according to the design specifications of the combustible gas detector, the detector may not provide an accurate output.
Read the Reduction in the Release of Volatile Organic Compounds (Storage and Loading of Volatile Petroleum Liquids) Regulations on the Justice Laws Website ↗

Made under Canadian Environmental Protection Act, 1999, S.C. 1999, c. 33.