Reduction in the Release of Volatile Organic Compounds (Storage and Loading of Volatile Petroleum Liquids) Regulations, SOR/2025-88
Section 13
Loading racks
Cite as Reduction in the Release of Volatile Organic Compounds (Storage and Loading of Volatile Petroleum Liquids) Regulations, SOR/2025-88, s. 13 · current to July 24, 2025 · regulation last amended July 5, 2025
Statute Watch
Get an alert when a bill in Parliament would change this section, and every time it moves.
The text
The operator of a facility must designate each loading rack that is used at the facility to load volatile petroleum liquids as belonging to one of the following categories:
(a) high benzene loading rack, in which case the loading rack may be used to load any volatile petroleum liquid;
(b) volatile petroleum liquid loading rack, in which case the loading rack may only be used to load a volatile petroleum liquid whose benzene concentration does not exceed 20% by weight;
(c) low throughput loading rack, in which case the loading rack may only be used to load a volatile petroleum liquid if the benzene concentration does not exceed 20% by weight and if either
(i) the loading rack and any fixed roof tank that receives volatile petroleum liquid from the loading rack are located more than 300 m from any occupied building and the following loading factors do not exceed 1:
(A) the total loading factor of the facility, and
(B) the maximum daily loading factor of the facility, or
(ii) the loading rack is located more than 50 km from any population centre and more than 1.5 km from any occupied building and the following loading factors do not exceed 2:
(A) the total loading factor of the facility and
(B) the maximum daily loading factor of the facility, or
(iii) the loading factor of the loading rack does not exceed 0.04; or
(d) remote loading rack, in which case the loading rack may only be used to load a volatile petroleum liquid if the vapour pressure of that liquid does not exceed 76 kPa, the benzene concentration of that liquid does not exceed 0.5% by weight and the loading rack is located more than 50 km from any population centre and more than 1.5 km from any occupied building.
Read the Reduction in the Release of Volatile Organic Compounds (Storage and Loading of Volatile Petroleum Liquids) Regulations on the Justice Laws Website ↗
Made under Canadian Environmental Protection Act, 1999, S.C. 1999, c. 33.
Bills in Parliament that would change this section 0
No bill we hold would amend or repeal this section.