Vessel Fire Safety Regulations, SOR/2017-14

Section 342

Cite as Vessel Fire Safety Regulations, SOR/2017-14, s. 342 · current to July 24, 2025 · regulation last amended November 23, 2022

Statute Watch

Get an alert when a bill in Parliament would change this section, and every time it moves.

The text

(1) Every machinery space must be capable of keeping the quantity of the extinguishing agent required by subsection 345(2), 346(2) or 347(2), as the case may be, within the space for at least 15 minutes. (2) The openings that can admit air to, or allow the extinguishing agent to escape from, a machinery space must be capable of being closed from outside the space. The means of closing must meet the requirements of subsection 329(4). (3) The openings that are used to vent a machinery space must be vented to outside the vessel and not to a location in the vicinity of a muster station. (4) If the release of the extinguishing agent into a machinery space could cause over- or under-pressurization that would affect the integrity of the space, measures must be in place to protect the integrity of the space.
Read the Vessel Fire Safety Regulations on the Justice Laws Website ↗

Made under Canada Shipping Act, 2001, S.C. 2001, c. 26.