Vessel Fire Safety Regulations, SOR/2017-14

Section 230

Cite as Vessel Fire Safety Regulations, SOR/2017-14, s. 230 · current to July 24, 2025 · regulation last amended November 23, 2022

Statute Watch

Get an alert when a bill in Parliament would change this section, and every time it moves.

The text

(1) If highly flammable liquids or liquefied gases are in a space, the space (a) must be directly accessible from an open deck and must not be otherwise accessible; and (b) must be provided with (i) if the deck area of the space is 4 m2 or more, a fixed gas fire-extinguishing system, fixed foam fire-extinguishing system or fixed pressure water-spraying fire-extinguishing system that meets the applicable requirements of the FSS Code for the system, and (ii) if the deck area of the space is less than 4 m2, (A) an ABC-type dry-chemical fire extinguisher that has a capacity of at least 4.5 kg, or (B) a fire extinguisher that has a fire-extinguishing capability at least equivalent to the fire extinguisher referred to in clause (A). (2) The pressure-adjusting devices and relief valves on cylinders that contain highly flammable liquids or liquefied gases must exhaust within the space where the cylinders are located. The space must be gastight if it adjoins another enclosed space.
Read the Vessel Fire Safety Regulations on the Justice Laws Website ↗

Made under Canada Shipping Act, 2001, S.C. 2001, c. 26.