The text
(1) Remote means must be provided to stop fuel oil transfer pumps, oil fuel unit pumps and other similar fuel pumps, and must be operable from outside the spaces served by those pumps. The main fire control station must be provided with a remote means to stop the pumps and with a visual indicator of whether the pumps are running.
(2) The remote means must be arranged so that a source of power to stop the pumps is provided
(a) from each individual motor control circuit; or
(b) from a dedicated source of power feeding an individual motor, or a group of motors connected to a motor control centre for a particular space, without any shunt-trip arrangements.
(3) A stop circuit of the remote means that is activated manually must be manually reset.
Read the Vessel Fire Safety Regulations on the Justice Laws Website ↗
Made under Canada Shipping Act, 2001, S.C. 2001, c. 26.