Vessel Fire Safety Regulations, SOR/2017-14
Section 219
Cite as Vessel Fire Safety Regulations, SOR/2017-14, s. 219 · current to July 24, 2025 · regulation last amended November 23, 2022
Statute Watch
Get an alert when a bill in Parliament would change this section, and every time it moves.
The text
(1) A ventilation duct that serves a machinery space of category A or a galley must not pass through an accommodation space, service space or control station unless
(a) the ventilation duct is made of steel that is supported, stiffened and of one of the following thicknesses:
(i) 3 mm, if the width or diameter of the duct is not more than 300 mm,
(ii) 5 mm, if the width or diameter of the duct is 760 mm or more, or
(iii) the thickness obtained by linear interpolation between the thicknesses set out in subparagraphs (i) and (ii), if the width or diameter of the duct is more than 300 mm but less than 760 mm; and
(b) the ventilation duct
(i) is insulated to an A-60 class fire rating throughout the accommodation space, service space or control station, or
(ii) meets the following requirements:
(A) it is fitted, at each of the space’s or station’s divisions that is penetrated by the duct, with a fail-safe automatic-closing fire damper that can be operated from both sides of the division, and
(B) it is insulated to an A-60 class fire rating from the machinery space or galley to a point at least 5 m beyond each fire damper.
(2) A ventilation duct that serves an accommodation space, service space or control station must not pass through a machinery space of category A or a galley unless
(a) the ventilation duct meets the requirements of paragraph (1)(a); and
(b) the ventilation duct
(i) is insulated to an A-60 class fire rating throughout the machinery space or galley, or
(ii) meets the following requirements:
(A) it is fitted, at each of the space’s or station’s divisions that is penetrated by the duct, with a fail-safe automatic-closing fire damper that can be operated from both sides of the division, and
(B) it is insulated to an A-60 class fire rating from the accommodation space, service space or control station to a point at least 5 m beyond each fire damper.
Read the Vessel Fire Safety Regulations on the Justice Laws Website ↗
Made under Canada Shipping Act, 2001, S.C. 2001, c. 26.