Vessel Fire Safety Regulations, SOR/2017-14
Section 218
Cite as Vessel Fire Safety Regulations, SOR/2017-14, s. 218 · current to July 24, 2025 · regulation last amended November 23, 2022
Statute Watch
Get an alert when a bill in Parliament would change this section, and every time it moves.
The text
(1) A ventilation opening must not be installed in or under a stairway enclosure door.
(2) Any ventilation opening in a door in a corridor bulkhead must be in the lower half of the door and must be fitted with a grille made of non-combustible material.
(3) The total net area of a ventilation opening in or under a door in a corridor bulkhead must not be more than 0.05 m2.
Read the Vessel Fire Safety Regulations on the Justice Laws Website ↗
Made under Canada Shipping Act, 2001, S.C. 2001, c. 26.