Vessel Fire Safety Regulations, SOR/2017-14
Section 120
Cite as Vessel Fire Safety Regulations, SOR/2017-14, s. 120 · current to July 24, 2025 · regulation last amended November 23, 2022
Statute Watch
Get an alert when a bill in Parliament would change this section, and every time it moves.
The text
(1) In addition to the requirements of regulation 9.4.1.1.2, every door in an “A” class division must meet the following requirements:
(a) the gap between the door leaf and its frame, as installed on board the vessel, must not exceed the gap measured when the door was tested in accordance with the FTP Code, but, in the case where the door was approved without a sill being part of the frame, the gap under the door, as installed on board the vessel, must not exceed the gap set out in regulation 9.4.1.1.2; and
(b) a grille or louvre must not be fitted in the door.
(2) The hose port requirements of regulation 9.4.1.1.8 apply in respect of every hose port fitted in a door in an “A” class division.
(3) If a ventilation duct passes through a main horizontal zone division on a passenger vessel, a fail-safe automatic-closing fire damper must be fitted in accordance with regulation 9.4.1.1.9, and the duct between the division and the damper must meet the requirements of that regulation.
(4) In addition to the requirements of regulations 9.4.1.1 and 9.4.1.2, every door in an “A” or “B” class division must be fitted with a thin metal identification plate that
(a) has clearly stamped on it the door manufacturer’s name, the “A” or “B” class rating, the type approval certificate number and the number of the drawing to which the door has been manufactured; and
(b) is screwed or riveted to either of the vertical edges of the door panel.
Read the Vessel Fire Safety Regulations on the Justice Laws Website ↗
Made under Canada Shipping Act, 2001, S.C. 2001, c. 26.