Energy Efficiency Regulations, 2016, SOR/2016-311
Section 705.2
Energy efficiency standards — three-phase and 1.2 kV voltage class
Cite as Energy Efficiency Regulations, 2016, SOR/2016-311, s. 705.2 · current to April 28, 2026 · regulation last amended October 9, 2025
Statute Watch
Get an alert when a bill in Parliament would change this section, and every time it moves.
The text
(1) In respect of dry-type transformers that are three-phase, in the 1.2 kV voltage class and manufactured on or after January 1, 2016, the energy efficiency standards set out column 2 of Table 1 to this section apply to dry-type transformers that have a kVA rating set out in column 1.
(2) In respect of dry-type transformers that are three-phase, in a voltage class greater than 1.2 kV and manufactured on or after January 1, 2016, the energy efficiency standards that are set out in relation to the product’s BIL rating set out in column 2 of Table 2 to this section apply to dry-type transformers that have a kVA rating set out in column 1.
(3) For the purposes of subsections (1) and (2), if the kVA rating of the product falls between the kVA ratings set out in two consecutive items in column 1 of the applicable table to this section, the energy efficiency standard for the product is an interpolation of the corresponding energy efficiency standards set out in column 2.
(4) The energy efficiency standard that is applicable to a dry-type transformer under this section is reduced by 0.11 if the transformer has multiple high-voltage windings and a voltage ratio other than 2:1.
(5) A dry-type transformer complies with the energy efficiency standard if it meets that standard when tested in accordance with testing procedures established by 10 C.F.R. Appendix A that are applicable to a dry-type transformer as defined in section 703.TABLE 1Column 1Column 2ItemkVA Rating% Efficiency When Tested at 35% of Nominal Load115.097.89230.098.23345.098.40475.098.605112.598.746150.098.837225.098.948300.099.029500.099.1410750.099.23111 000.099.28TABLE 2Column 1Column 2ItemkVA Rating% Efficiency When Tested at 50% of Nominal Load20-45 kV BIL> 45-95 kV BIL> 95-199 kV BIL115.097.5097.1896.80230.097.9097.6397.30345.098.1097.8697.60475.098.3398.1397.905112.598.5298.3698.106150.098.6598.5198.207225.098.8298.6998.578300.098.9398.8198.699500.099.0998.9998.8910750.099.2199.1299.02111 000.099.2899.2099.11121 500.099.3799.3099.21132 000.099.4399.3699.28142 500.099.4799.4199.33153 000.099.4799.4199.33163 750.099.4799.4199.33175 000.099.4799.4199.33187 500.099.4899.4199.39
Read the Energy Efficiency Regulations, 2016 on the Justice Laws Website ↗
Made under Energy Efficiency Act, S.C. 1992, c. 36.
Bills in Parliament that would change this section 0
No bill we hold would amend or repeal this section.