(1) Except as provided in subsection (7), storage tanks shall be securely installed on solid foundations of steel or concrete with reinforced concrete footings extending below the frost line, or resting on bedrock. (2) Except as provided in subsection (6), steel foundations shall be fireproofed with a material having a fire resistance of not less than 2 hours. (3) Foundations shall be of sufficient width and thickness to adequately support the tank and its contents. (4) Provision shall be made for the thermal expansion and contraction of a tank. (5) Only two saddles shall be used on horizontal tanks. (6) Steel saddles, which are welded to a tank, need not be fireproofed if the tank capacity does not exceed 500 Imperial gallons or if the over-all height of the saddle does not exceed 18 inches. (7) Footings for tanks with a water capacity less than 500 Imperial gallons need not be installed below frost line if adequate provision is made to protect the piping against the effects of setting.