Flammable Liquids Bulk Storage Regulations, C.R.C., c. 1148
Section 24
Cite as Flammable Liquids Bulk Storage Regulations, C.R.C., c. 1148, s. 24 · current to July 24, 2025 · regulation last amended June 18, 2015
Statute Watch
Get an alert when a bill in Parliament would change this section, and every time it moves.
The text
(1) All flammable liquid storage tanks shall be equipped with vent pipes or devices sized to keep the internal pressure or vacuum within the design limits of the tank.
(2) Except as provided in subsection (3), all vents on storage tanks containing Class I flammable liquids shall be equipped with corrosion resistant flame arrestors or breather valves or venting devices that normally remain closed.
(3) Notwithstanding subsection (2), open vents may be installed on a storage tank containing a Class I flammable liquid if the capacity does not exceed 3,000 Imperial gallons.
(4) All above ground storage tanks shall be provided with a means of emergency pressure relief. In a vertical storage tank, this may take the form of a weak seam or joint on the top of the tank or between the head and the shell of the storage tank. The total venting capacity of both normal and emergency vents shall be sufficient to prevent violent rupture of the storage tank when exposed to fire.
(5) Gauge hatch covers shall be fitted with a spark resistant material.
(6) The lower end of the vent pipe on all storage tanks shall not extend more than one inch through the top of the storage tank and shall be installed so that the pipe will drain into the storage tank without traps or bends in which liquid can collect.
(7) The discharge point of all storage tank vent pipes shall be located outside buildings so that flammable vapours will not enter building openings, or be trapped under eaves or other obstructions, or be exposed to a source of ignition.
(8) For Class I flammable liquids, the point of discharge of a vent pipe on a below ground storage tank shall be higher than the fill pipe opening, shall discharge upwards, and shall be at least 12 feet above adjacent ground level.
(9) The discharge point of vent pipes on Class II below ground flammable liquid storage tanks shall be located above the highest recorded snow level. The vent pipes may be fitted with return bends, coarse screens or other devices to minimize the ingress of foreign material.