Flammable Liquids Bulk Storage Regulations, C.R.C., c. 1148

Section 23

Cite as Flammable Liquids Bulk Storage Regulations, C.R.C., c. 1148, s. 23 · current to July 24, 2025 · regulation last amended June 18, 2015

Statute Watch

Get an alert when a bill in Parliament would change this section, and every time it moves.

The text

If the ground resistance of a storage tank exceeding 3,000 Imperial gallons is greater than 15 ohms, ground rods or other grounding devices shall be used.
Read the Flammable Liquids Bulk Storage Regulations on the Justice Laws Website ↗

Made under Railway Safety Act, R.S.C. 1985, c. 32 (4th Supp.).

Bills in Parliament that would change this section 0

No bill we hold would amend or repeal this section.