HEALTH CARE AND RESIDENTIAL FACILITIES, O. Reg. 67/93

Section 66

Cite as HEALTH CARE AND RESIDENTIAL FACILITIES, O. Reg. 67/93, s. 66 · current to November 11, 2026 · consolidated from June 9, 2025 · read from e-Laws on November 16, 2026

The text

(1) The power supply to electrical installations, equipment or power lines shall be disconnected, locked out of service and tagged before any work is done, and while any work is being done, on or near the installations, equipment or power lines. (2) Locking out and tagging are not required, (a) if the power lines are adequately grounded with a visible grounding mechanism; or (b) if the voltage is less than 300 volts and there is no locking device for the circuit breakers or fuses and procedures are in place adequate to ensure that the circuit is not inadvertently energized. (3) Before beginning the work, each worker shall determine if the power supply is disconnected. (4) If locking out and tagging are not required, the employer shall ensure that the procedures set out in clause (2) (b) are carried out. (5) This section does not apply if it is not practicable to disconnect electrical installations, equipment or power lines from the power supply before working on, or near, the installations, equipment or power lines. O. Reg. 67/93, s. 66.
Read the HEALTH CARE AND RESIDENTIAL FACILITIES on e-Laws ↗

Made under Occupational Health and Safety Act, R.S.O. 1990, c. O.1.