HEALTH CARE AND RESIDENTIAL FACILITIES, O. Reg. 67/93
Section 101
Cite as HEALTH CARE AND RESIDENTIAL FACILITIES, O. Reg. 67/93, s. 101 · current to November 11, 2026 · consolidated from June 9, 2025 · read from e-Laws on November 16, 2026
The text
(1) If more than 235 litres of flammable liquids are being stored, the liquids shall be stored,
(a) outdoors, remote from any means of egress:
(b) in a building used solely for the storage of flammable liquids; or
(c) within a workplace, in a storage room that is used solely for the storage of flammable liquids and that complies with subsection (2).
(2) The storage room shall,
(a) be separated from the rest of the building with partitions that have at least a one-hour fire resistance rating;
(b) be equipped with,
(i) liquid-tight seals between interior walls and the floor and a liquid-tight ramped sill at any door opening in an interior wall, or
(ii) other means to prevent leakage or spillage of the flammable liquid from the storage room to another part of the workplace in the building;
(c) be equipped with doors that are side hinged to swing outward and that are self-closing;
(d) be equipped with a drain connected to a holding tank of sufficient capacity to contain any possible leakage or spillage;
(e) be provided with a ventilation system that is adequate to render the atmosphere free of any accumulation of hazardous gas or vapour; and
(f) if the flammable liquids are in opened containers or have flash points below 22.8 degrees Celsius and boiling points below 37.8 degrees Celsius,
(i) be equipped with a spark-resistant floor,
(ii) be equipped with adequate explosion venting to the outdoors, and
(iii) have no potential source of ignition.
(3) If the quantity of flammable liquids to be stored indoors is 235 litres or less, the liquids shall be stored,
(a) in sealed containers of no more than twenty-three litres capacity each; or
(b) subject to section 106, in a metal cabinet of double-walled construction with a 3-point door latch and a liquid-tight door sill raised at least fifty-five millimetres above the floor. O. Reg. 67/93, s. 101.
Read the HEALTH CARE AND RESIDENTIAL FACILITIES on e-Laws ↗
Made under Occupational Health and Safety Act, R.S.O. 1990, c. O.1.