CONSTRUCTION PROJECTS, O. Reg. 213/91

Section 381

Cite as CONSTRUCTION PROJECTS, O. Reg. 213/91, s. 381 · current to November 11, 2026 · consolidated from April 20, 2026 · read from e-Laws on November 16, 2026

The text

(1) A smoke line shall be provided from each work face of a work chamber if an air lock or bulkhead is located between the chamber and the surface. O. Reg. 213/91, s. 381 (1). (2) Each smoke line shall extend to a point less than 15 metres from a work face. O. Reg. 213/91, s. 381 (2); O. Reg. 142/17, s. 41 (1). (3) Each smoke line shall have two quick opening valves at least 100 millimetres in diameter, (a) one located less than 17 metres from the work face; and (b) one located between the air lock closest to the work chamber and the work chamber and less than two metres from the air lock. O. Reg. 213/91, s. 381 (3); O. Reg. 142/17, s. 41 (2, 3). (4) Each smoke line shall be at least 100 millimetres in diameter and shall have a readily-accessible outlet above ground, (a) that has a quick opening valve at least 100 millimetres in diameter; (b) that is clearly marked with a sign stating “SMOKE LINE – TO BE USED ONLY IN CASE OF EMERGENCY”; and (c) that is sealed to prevent the inadvertent opening of the valve. O. Reg. 213/91, s. 381 (4). (5) Each smoke line shall extend from inside the work chamber to above ground and shall pass vertically through either the air lock or the bulkhead between the work chamber and air at atmospheric pressure. O. Reg. 213/91, s. 381 (5).