CONSTRUCTION PROJECTS, O. Reg. 213/91

Section 345

Cite as CONSTRUCTION PROJECTS, O. Reg. 213/91, s. 345 · current to November 11, 2026 · consolidated from April 20, 2026 · read from e-Laws on November 16, 2026

The text

(1) A standpipe connected to a source of water or connected to other pipes above ground shall be installed in every air lock and work chamber at a project. O. Reg. 213/91, s. 345 (1). (2) A standpipe shall have, (a) valves that isolate the standpipe from the rest of the fire prevention system; (b) a fitting that is controlled by a valve installed on the standpipe on the work chamber side of the bulkhead and by a valve inside the material lock; (c) a fitting and valve similar to that described in clause (b) installed at the end of the standpipe nearest to the work face; and (d) the location of the fittings and valves clearly marked. O. Reg. 213/91, s. 345 (2). (3) A fitting described in clause (2) (b) shall be such that a fire hose of the local fire department can be connected to it. O. Reg. 213/91, s. 345 (3).
Read the CONSTRUCTION PROJECTS on e-Laws ↗

Made under Occupational Health and Safety Act, R.S.O. 1990, c. O.1.