CONSTRUCTION PROJECTS, O. Reg. 213/91
Section 251
Cite as CONSTRUCTION PROJECTS, O. Reg. 213/91, s. 251 · current to November 11, 2026 · consolidated from April 20, 2026 · read from e-Laws on November 16, 2026
The text
(1) If the diameter of a tunnel will be equal to or greater than 1.5 metres when it is completed, a standpipe, a fire line and a hose shall be provided in the tunnel. O. Reg. 213/91, s. 251 (1).
(2) A siamese connection shall be provided on the fire line at the surface of the shaft. O. Reg. 213/91, s. 251 (2).
Read the CONSTRUCTION PROJECTS on e-Laws ↗