(1) This section applies if electric blasting caps are used on a project. O. Reg. 213/91, s. 202 (1).
(2) The protective shunt shall not be removed from the leg wire until connections are made. O. Reg. 213/91, s. 202 (2).
(3) The firing circuit shall be short-circuited while the leads from the blasting caps are being connected to each other and to the firing cables. O. Reg. 213/91, s. 202 (3).
(4) The short circuit shall not be removed until immediately before blasting and until all workers have left the area affected by the blasting operations. O. Reg. 213/91, s. 202 (4).
(5) The source of energy for a blasting operation shall be disconnected from the firing circuit immediately after firing. O. Reg. 213/91, s. 202 (5).