CONSTRUCTION PROJECTS, O. Reg. 213/91

Section 191

Cite as CONSTRUCTION PROJECTS, O. Reg. 213/91, s. 191 · current to November 11, 2026 · consolidated from April 20, 2026 · read from e-Laws on November 16, 2026

The text

(1) This section applies instead of section 190 if work is to be done on or near energized exposed parts of electrical equipment or of an electrical installation or conductor and, (a) it is not reasonably possible to disconnect the equipment, installation or conductor from the power supply before working on or near the energized exposed parts; (b) the equipment, installation or conductor is rated at a nominal voltage of 600 volts or less, and disconnecting the equipment, installation or conductor would create a greater hazard to a worker than proceeding without disconnecting it; or (c) the work consists only of diagnostic testing of the equipment, installation or conductor. O. Reg. 627/05, s. 7. (2) Subsection (10) applies, in addition to subsections (3) to (9), if the equipment, installation or conductor is nominally rated at, (a) greater than 400 amperes and greater than 200 volts; or (b) greater than 200 amperes and greater than 300 volts. O. Reg. 627/05, s. 7. (3) Only a worker who meets the requirements of clause 182 (1) (a) or (b) shall perform the work. O. Reg. 627/05, s. 7. (4) The constructor shall, (a) ensure that written measures and procedures for complying with this section are established and implemented, so that workers are adequately protected from electrical shock and burn; and (b) make a copy of the written measures and procedures available to every employer on the project. O. Reg. 627/05, s. 7. (5) Before a worker begins work to which this section applies, the employer shall provide a copy of the written measures and procedures to the worker and explain them to him or her. O. Reg. 627/05, s. 7. (6) The worker shall follow the written procedures. O. Reg. 627/05, s. 7. (7) A worker shall use mats, shields or other protective devices or equipment, including personal protective equipment, adequate to protect the worker from electrical shock and burn. O. Reg. 627/05, s. 7. (8) If the electrical equipment, installation or conductor is rated at a nominal voltage of 300 volts or more, an adequately equipped competent worker who can perform rescue operations, including cardiopulmonary resuscitation, shall be stationed so that he or she can see the worker who is performing the work. O. Reg. 627/05, s. 7. (9) Subsection (8) does not apply if the work consists only of diagnostic testing of the equipment, installation or conductors. O. Reg. 627/05, s. 7. (10) In the case of equipment or of an installation or conductor described in subsection (2), a worker shall not perform the work unless the following additional conditions are satisfied: 1. The owner of the equipment, installation or conductor has provided the employer and the constructor with a record showing that it has been maintained according to the manufacturer’s specifications. 2. A copy of the maintenance record is readily available at the project. 3. The employer has determined from the maintenance record that the work on the equipment, installation or conductor can be performed safely without disconnecting it. 4. Before beginning the work, the worker has verified that paragraphs 1, 2 and 3 have been complied with. O. Reg. 627/05, s. 7.
Read the CONSTRUCTION PROJECTS on e-Laws ↗

Made under Occupational Health and Safety Act, R.S.O. 1990, c. O.1.