CONSTRUCTION PROJECTS, O. Reg. 213/91

Section 188

Cite as CONSTRUCTION PROJECTS, O. Reg. 213/91, s. 188 · current to November 11, 2026 · consolidated from April 20, 2026 · read from e-Laws on November 16, 2026

The text

(1) This section applies unless the conditions set out in clauses 189 (a) and (b) are satisfied. O. Reg. 627/05, s. 7. (2) No object shall be brought closer to an energized overhead electrical conductor with a nominal phase-to-phase voltage rating set out in Column 1 of the Table to this subsection than the distance specified opposite to it in Column 2. TABLE Item | Column 1 Nominal phase-to-phase voltage rating | Column 2 Minimum distance 1. | 750 or more volts, but no more than 150,000 volts | 3 m 2. | more than 150,000 volts, but no more than 250,000 volts | 4.5 m 3. | more than 250,000 volts | 6 m (3) Subsections (4) to (9) apply if a crane, similar hoisting device, backhoe, power shovel or other vehicle or equipment is operated near an energized overhead electrical conductor and it is possible for a part of the vehicle or equipment or its load to encroach on the minimum distance permitted under subsection (2). O. Reg. 627/05, s. 7. (4) A constructor shall, (a) establish and implement written measures and procedures adequate to ensure that no part of a vehicle or equipment or its load encroaches on the minimum distance permitted by subsection (2); and (b) make a copy of the written measures and procedures available to every employer on the project. O. Reg. 627/05, s. 7. (5) The written measures and procedures shall include taking the following precautions to protect workers: 1. Adequate warning devices, visible to the operator and warning of the electrical hazard, shall be positioned in the vicinity of the hazard. 2. The operator shall be provided with written notification of the electrical hazard before beginning the work. 3. A legible sign, visible to the operator and warning of the potential electrical hazard, shall be posted at the operator’s station. O. Reg. 627/05, s. 7. (6) Before a worker begins work that includes an activity described in subsection (3), the employer shall provide a copy of the written measures and procedures to the worker and explain them to him or her. O. Reg. 627/05, s. 7. (7) The worker shall follow the written measures and procedures. O. Reg. 627/05, s. 7. (8) A competent worker, designated as a signaller, shall be stationed so that he or she is in full view of the operator and has a clear view of the electrical conductor and of the vehicle or equipment, and shall warn the operator each time any part of the vehicle or equipment or its load may approach the minimum distance. O. Reg. 627/05, s. 7. (9) Section 106 also applies with respect to the signaller designated under subsection (8). O. Reg. 627/05, s. 7.
Read the CONSTRUCTION PROJECTS on e-Laws ↗

Made under Occupational Health and Safety Act, R.S.O. 1990, c. O.1.