CONSTRUCTION PROJECTS, O. Reg. 213/91
Section 141.4
Cite as CONSTRUCTION PROJECTS, O. Reg. 213/91, s. 141.4 · current to November 11, 2026 · consolidated from April 20, 2026 · read from e-Laws on November 16, 2026
The text
(1) The owner of a building or structure shall ensure that all fixed supports identified in the roof plan are inspected, maintained and tested in accordance with clause 11 (Inspection and Testing) of CSA Standard Z271-10 and the manufacturer’s instructions. O. Reg. 242/16, s. 11.
(2) Without limiting the generality of subsection (1), the owner shall ensure that a fixed support identified in the roof plan is inspected by an engineer,
(a) before being used for the first time after it is installed and after every time that it is repaired or modified;
(b) as often as necessary and at least as often as recommended by the manufacturer of the fixed support;
(c) at least once within the 12-month period preceding its use; and
(d) if an engineer, an employer, a supervisor or a worker advises the owner that there are reasonable grounds to believe the fixed support is defective or not adequate to support the suspended work platform, boatswain’s chair or lifeline. O. Reg. 242/16, s. 11; O. Reg. 375/22, s. 5.
(3) An owner who has been advised under clause (2) (d) shall ensure that the fixed support in question is not used until the requirements in subsections (4) and (5) are met, as applicable. O. Reg. 242/16, s. 11.
(4) The engineer who performs an inspection under subsection (2) shall prepare a written report that,
(a) indicates whether the fixed support meets the requirements of section 141.1 and is adequate for the purposes of attaching a suspended work platform, boatswain’s chair or lifeline; and
(b) if the fixed support is not adequate, indicates the defects and hazardous conditions of the fixed support. O. Reg. 242/16, s. 11; O. Reg. 375/22, s. 5.
(5) A fixed support that has been identified in the report of the engineer as having a defect or hazardous condition shall not be used until the owner of the building or structure ensures that,
(a) the defect or hazardous condition of the fixed support has been repaired, modified or corrected; and
(b) the fixed support has been inspected and tested by an engineer in accordance with clause 11.3.3 (Anchorage connectors) of CSA Standard Z271-10 and the engineer has determined the fixed support to be adequate to support a suspended work platform, boatswain’s chair or lifeline. O. Reg. 242/16, s. 11; O. Reg. 375/22, s. 5.
(6) The owner of the building or structure shall, respecting a fixed support,
(a) keep a permanent record, in accordance with clause 13 (Equipment Log) of CSA Standard Z271-10, of all inspections, tests, repairs, modifications and maintenance of the fixed support as long as the fixed support is used;
(b) make the record available, on request, to an inspector; and
(c) make the record available, on request, to a constructor of a project where workers are to use a suspended work platform system or boatswain’s chair and lifelines, if any. O. Reg. 242/16, s. 11.
(7) No employer or constructor shall permit a worker to use a fixed support unless the employer or constructor has ensured that the fixed support has been inspected, maintained and tested as required by this section, and, if applicable, the requirements in subsections (4) and (5) are met. O. Reg. 242/16, s. 11.
Read the CONSTRUCTION PROJECTS on e-Laws ↗
Made under Occupational Health and Safety Act, R.S.O. 1990, c. O.1.