Fire doors in an underground mine shall,
(a) where practical, be installed to close off the shaft or main entrance to the mine and the mine openings directly associated with it from the other workings;
(b) be installed to close off,
(i) service garages, and
(ii) oil storage areas where a total of more than 500 litres of oil, grease or flammable liquid are stored;
(c) have at least a one hour fire-resistance rating; and
(d) be maintained in proper order and kept clear of all obstructions so as to be readily usable at all times. R.R.O. 1990, Reg. 854, s. 39.
Read the MINES AND MINING PLANTS on e-Laws ↗