MINES AND MINING PLANTS, R.R.O. 1990, Reg. 854
Section 28
Cite as MINES AND MINING PLANTS, R.R.O. 1990, Reg. 854, s. 28 · current to November 11, 2026 · consolidated from July 1, 2025 · read from e-Laws on November 16, 2026
The text
(1) Fire extinguishing equipment of suitable type and size for use on a fire shall be provided,
(a) at a fire hazard area;
(b) where an electrical installation or equipment may be a fire hazard;
(c) in or about a headframe;
(d) in a building or structure on surface where a fire might endanger the mine entrance; and
(e) at a shaft station in an underground mine. R.R.O. 1990, Reg. 854, s. 28 (1).
(2) A fire suppression system consisting of sprinklers, foam or other suitable means of suppressing fire shall be provided,
(a) in an underground mine,
(i) on equipment containing more than 100 litres of flammable hydraulic fluids,
(ii) in every storage area where more than 500 litres of oil, grease or flammable liquids are stored,
(iii) in every service garage, and
(iv) in every permanent fuelling station; and
(b) on the surface, in a building or structure, except a fan house, located above or adjacent to an opening to an underground mine. R.R.O. 1990, Reg. 854, s. 28 (2); O. Reg. 486/99, s. 1.
(3) At least once each month in an underground mine,
(a) fire extinguishing equipment;
(b) fire suppression systems;
(c) fire hydrants; and
(d) fire doors,
shall be inspected by a competent person who shall report in writing thereon to the supervisor in charge of the underground mine. R.R.O. 1990, Reg. 854, s. 28 (3).
Read the MINES AND MINING PLANTS on e-Laws ↗
Made under Occupational Health and Safety Act, R.S.O. 1990, c. O.1.