INDUSTRIAL ESTABLISHMENTS, R.R.O. 1990, Reg. 851

Section 65

Cite as INDUSTRIAL ESTABLISHMENTS, R.R.O. 1990, Reg. 851, s. 65 · current to November 11, 2026 · consolidated from July 1, 2022 · read from e-Laws on November 16, 2026

The text

(1) Subject to subsection (2), a collector that collects aluminum, magnesium or other fine dust of an easily ignitable nature shall be located, (a) outdoors; or (b) in a room used solely for the housing of dust-collecting equipment which is, (i) separated from the rest of the building by a dust-tight partition having a minimum fire-resistance rating of one hour, and (ii) constructed to provide explosion venting to the outdoors. (2) Subsection (1) does not apply to a collector, (a) that uses an inert liquid as a medium to collect dust; (b) that is used for a wood-working operation other than wood flour manufacturing and having less than 0.47 cubic metres per second capacity; (c) that will safely contain explosions; or (d) that will resist explosions and is equipped with effective explosion venting to the outdoors. R.R.O. 1990, Reg. 851, s. 65.
Read the INDUSTRIAL ESTABLISHMENTS on e-Laws ↗

Made under Occupational Health and Safety Act, R.S.O. 1990, c. O.1.