INDUSTRIAL ESTABLISHMENTS, R.R.O. 1990, Reg. 851

Section 42.1

Cite as INDUSTRIAL ESTABLISHMENTS, R.R.O. 1990, Reg. 851, s. 42.1 · current to November 11, 2026 · consolidated from July 1, 2022 · read from e-Laws on November 16, 2026

The text

(1) This section applies and section 42 does not apply if it is not practical to disconnect electrical installations, equipment or conductors from the power supply before working on, or near, live exposed parts of the installations, equipment or conductors. O. Reg. 630/94, s. 1. (2) The worker shall use rubber gloves, mats, shields and other protective equipment and procedures adequate to ensure protection from electrical shock and burns while performing the work. O. Reg. 630/94, s. 1. (3) If the installation, equipment or conductor is operating at a nominal voltage of 300 volts or more, a suitably equipped competent person who is able to recognize the hazards and perform rescue operations, including artificial respiration, shall be available and able to see the worker who is performing the work. O. Reg. 630/94, s. 1. (4) Subsection (3) does not apply to equipment testing and trouble-shooting operations. O. Reg. 630/94, s. 1.
Read the INDUSTRIAL ESTABLISHMENTS on e-Laws ↗

Made under Occupational Health and Safety Act, R.S.O. 1990, c. O.1.