INDUSTRIAL ESTABLISHMENTS, R.R.O. 1990, Reg. 851

Section 22

Cite as INDUSTRIAL ESTABLISHMENTS, R.R.O. 1990, Reg. 851, s. 22 · current to November 11, 2026 · consolidated from July 1, 2022 · read from e-Laws on November 16, 2026

The text

(1) Subject to subsections (2), (3) and (4), where not required for immediate use, flammable liquids shall be, (a) in sealed containers; and (b) located, (i) outdoors and remote from any means of egress, (ii) in a building not used for any other purpose, or (iii) in a room, (A) separated from the rest of the building with partitions having, 1. at least a one-hour fire-resistance rating, and 2. self-closing doors, hinged to swing outwardly on their vertical axes, (B) equipped with, 1. a drain connected to a dry sump or holding tank, and 2. liquid-tight seals between interior walls and floor and a liquid-tight ramped sill at any door opening, which is not in an exterior wall, and (C) having natural ventilation to the outdoors by upper and lower exterior wall gravity louvres. R.R.O. 1990, Reg. 851, s. 22 (1); O. Reg. 420/10, s. 5. (2) Where not required for immediate use, flammable liquids, (a) in opened containers; or (b) having a flash point below 22.8° Celsius and a boiling point below 37.8° Celsius, shall, (c) comply with the requirements of clause (1) (b); (d) be stored in facilities having no potential source of ignition; and (e) when located in a room, be located in a room equipped with, (i) explosion venting to the outdoors, and (ii) a spark resistant floor. R.R.O. 1990, Reg. 851, s. 22 (2). (3) A maximum of 235 litres of flammable liquids may be stored, (a) in sealed containers of not more than twenty-three litre capacity each; or (b) in a metal cabinet of double walled construction with a 3-point door latch and a liquid-tight door sill raised at least fifty millimetres above the floor. R.R.O. 1990, Reg. 851, s. 22 (3). (4) An area where flammable liquids are dispensed shall have, (a) mechanical ventilation from floor level to the outdoors at the rate of eighteen cubic metres per hour per square metre of floor area; and (b) containers and dispensing equipment bonded and grounded when flammable liquid is dispensed. R.R.O. 1990, Reg. 851, s. 22 (4).
Read the INDUSTRIAL ESTABLISHMENTS on e-Laws ↗

Made under Occupational Health and Safety Act, R.S.O. 1990, c. O.1.