INDUSTRIAL ESTABLISHMENTS, R.R.O. 1990, Reg. 851
Section 18
Cite as INDUSTRIAL ESTABLISHMENTS, R.R.O. 1990, Reg. 851, s. 18 · current to November 11, 2026 · consolidated from July 1, 2022 · read from e-Laws on November 16, 2026
The text
(1) Subject to subsection (2), an access ladder fixed in position shall,
(a) be vertical;
(b) have rest platforms at not more than nine metre intervals;
(c) be offset at each rest platform;
(d) where the ladder extends over five metres, above grade, floor or landing, have a safety cage commencing not more than 2.2 metres above grade, floor or landing and continuing at least ninety centimetres above the top landing with openings to permit access by a worker to rest platforms or to the top landing;
(e) have side rails that extend ninety centimetres above the landing; and
(f) have rungs which are at least fifteen centimetres from the wall and spaced at regular intervals. R.R.O. 1990, Reg. 851, s. 18 (1); O. Reg. 420/10, s. 4.
(2) Subsection (1) does not apply to an access ladder on a tower, water tank, chimney or similar structure which has a safety device which will provide protection should a worker using the ladder fall. R.R.O. 1990, Reg. 851, s. 18 (2).
Read the INDUSTRIAL ESTABLISHMENTS on e-Laws ↗