PUBLIC POOLS, R.R.O. 1990, Reg. 565
Section 7
Water quality
Cite as PUBLIC POOLS, R.R.O. 1990, Reg. 565, s. 7 · current to November 11, 2026 · consolidated from January 1, 2025 · read from e-Laws on November 16, 2026
The text
(1) Every owner and every operator of a public pool or public spa shall ensure that the clean water and the make-up water are free from contamination that may be injurious to the health of the bathers. O. Reg. 494/17, s. 5.
(2) Every owner and every operator of a public pool or public spa shall ensure that the pool or spa water and its circulation system is separate from the potable water supply and from the sewer or drainage system into which it drains by air gaps or other devices that prevent the water in the pool or spa or its circulation system from flowing back into the potable water supply, and the water in the sewer or drainage system from flowing back into the pool or spa or its circulation system. O. Reg. 494/17, s. 5.
(3) Every owner and every operator of a public pool or public spa shall ensure that the pool or spa water is maintained free from visible matter that may be hazardous to the health or safety of the bathers. O. Reg. 494/17, s. 5.
(4) In the case of a public pool, every owner and every operator, other than an owner and operator of a modified pool or a wave action pool, shall ensure that the pool water is of a clarity to permit a black disc 150 millimetres in diameter on a white background located on the bottom of the pool at its deepest point to be clearly visible from a point on the deck nine metres away from the disc. O. Reg. 494/17, s. 5.
(5) In the case of a public pool, every owner and every operator of a modified pool shall ensure that the pool water is of a clarity to permit a lifeguard occupying the lifeguard control station that is least affected by reflections from the water surface to see at a distance of 35 metres from the control station the continuous black marking referred to in subsection 18 (3) on the bottom of the pool where the water is 1.20 metres in depth. O. Reg. 494/17, s. 5.
(6) Every owner and every operator of a wave action pool shall ensure that the pool water is of a clarity to permit a black disc 150 millimetres in diameter on a white background located on the bottom of the pool in the area of its greatest depth to be clearly visible from a point on the deck nine metres away from the disc when no waves are being induced in the pool. O. Reg. 494/17, s. 5.
(7) Every owner and every operator of a public spa shall ensure that the public spa water is of a clarity to permit the owner or operator to see the lowest water outlet drain when the spa water is in a non-turbulent state. O. Reg. 494/17, s. 5.
(8) Every owner and every operator of a public pool or public spa shall ensure that the pool or spa water is treated with chlorine, a chlorine compound or a bromine compound by means of a chemical feeder, and is maintained so that in every part of the pool or spa, at all times during the daily use period,
(a) the total alkalinity is maintained in the range of 60 ppm to 180 ppm;
(b) the pH value is within the range of 7.2 to 7.8;
(c) there is a residual of free available chlorine in every part of a public pool, other than a public floatation pool or a public cold plunge pool of at least 0.5 ppm but not more than 10 ppm, and a residual of free available chlorine or total bromine in every part of a public spa of at least 5 ppm but not more than 10 ppm;
(d) where a pool is not a wave action pool and a bromine compound is used, there is a total bromine residual of not less than 2 ppm and not more than 8 ppm;
(e) where a pool is a wave action pool and a bromine compound is used, there is a total bromine residual of not less than 3 ppm and not more than 10 ppm;
(e.1) where a pool is a public floatation pool or a public cold plunge pool, there is a residual of free available chlorine of at least 5 ppm and not more than 10 ppm in every part of the public floatation pool or public cold plunge pool;
(e.2) where a pool is a hot water pool that operates at a temperature of 35 degrees Celsius or greater, there is a residual of free available chlorine or total bromine in every part of the hot water pool of at least 5 ppm but not more than 10 ppm;
(f) if the pool or spa is equipped with an automatic sensing device, the Oxidation Reduction Potential value is not less than 600 mV and not greater than 900 mV; and
(g) where the medical officer of health determines that the health of the bathers may be affected, there is such higher minimum or maximum chlorine or bromine residual than required under clause (c), (d) or (e) as the medical officer of health may require in writing. O. Reg. 494/17, s. 5; O. Reg. 502/24, s. 5 (1-4).
(8.1) In addition to the requirements of subsection 7 (8), where a pool is a public floatation pool, it shall be equipped with a secondary treatment system of ultraviolet light disinfection that is appropriately sized for the public floatation pool and the system shall have an automatic shut off device or an audible and visual alarm in case of system failure. O. Reg. 502/24, s. 5 (5).
(9) The method used in determining the free available chlorine residual referred to in clause (8) (c) and, if applicable, paragraph 1 of subsection (10), shall be such that chloramines or other compounds that may be present in the pool or spa do not affect the determination. O. Reg. 494/17, s. 5.
(10) Every owner and every operator of a public pool or public spa shall ensure that the following is complied with:
1. Where cyanurate stabilization is maintained in outdoor pools there must be a residual of free available chlorine of not less than 1 ppm and not more than 10 ppm, in association with a cyanuric acid concentration of not greater than 60 milligrams per litre.
2. For indoor pools (totally or partially covered by a roof) and all spas, no cyanurate stabilization shall be used. O. Reg. 494/17, s. 5.
(11) Every operator of a public pool or public spa shall test and record the following regarding the pool or spa water each operating day, by means of manual test methods, a minimum of 30 minutes prior to opening:
1. Total alkalinity
2. pH value.
3. Free available chlorine and total chlorine or bromine residual.
4. Water clarity.
5. Water temperature, in the case of spas and in the case of hot water pools that operate at a temperature of 35 degrees Celsius or greater. O. Reg. 494/17, s. 5; O. Reg. 502/24, s. 5 (6).
(12) Where the pool or spa has an automatic sensing device, the requirements provided for in subsection (11) must be further checked and recorded at least every four hours until the daily use period has ended. For pools and spas without an automatic sensing device, the requirements provided for in subsection (11) must be further manually checked and recorded at least every two hours until the daily use period has ended. O. Reg. 494/17, s. 5.
(13) Every operator of a public pool shall add make-up water to the pool during each operating day in a minimum amount of 15 litres per bather as determined by a water meter installed for the purpose. O. Reg. 494/17, s. 5.
(14) Every operator of a public spa with a volume that exceeds 4,000 litres shall add make-up water to the spa during each operating day in an amount that is a minimum of 15 litres per bather use, to a maximum of 20 per cent of the total spa volume. O. Reg. 494/17, s. 5.
(15) Every owner and every operator of a public pool or a public spa to which subsection (13) or (14) applies shall ensure that a water meter is provided that registers the volume of all make-up water that is added to the pool or spa, as the case may be. O. Reg. 494/17, s. 5.
(16) Every operator of a public spa with a volume that is 4,000 litres or less shall drain to waste and refill the total volume of water in the public spa in accordance with the following formula:
WRI = V ÷ (10 × U)
where,
WRI = the maximum number of operating days that may elapse between drainings, rounded up to a whole number,
V = the total volume of the spa in litres, and
U = the total estimated number of bather uses per operating day.
(17) An operator who drains a public spa in accordance with subsection (16) shall, before refilling the spa, inspect all parts of the spa including, but not limited to, drain covers, suction fittings and all emergency equipment within the spa, and ensure that they are properly secured and operational. O. Reg. 494/17, s. 5.